Artesis Plant Condition Monitor (PCM)

Technical Specifications

 

PCM LV
for low voltage generators

PCM MV & HV
for medium and high voltage generators

Dimensions
(W x H x L)

96mm x 96mm x 140mm

Front panel mounting

96mm x 96mm x 140mm

Front panel mounting

Enclosure

Aluminium, RAL 7032 surface protection

Aluminium, RAL 7032 surface protection

Operations

Continuous

Continuous

Ambient temperature

0-40c (Humidity %90 RH non-condensing)

0-40c (Humidity %90 RH non-condensing)

Class

IP20

IP20

Applicable power range

Low voltage generators

Medium and high voltage generators

Interfaces

RS 485 serial I/0, Modbus, Artebus

RS 485 serial I/0, Modbus, Artebus

Digital outputs

1 assignable relay output, user programmable NC/NO contacts

1 assignable relay output, user programmable NC/NO contacts

Update period

60-120 seconds

60-120 seconds

Input Line Power Specifications

Voltage

90-240 VAC

90-240 VAC

Power

15 W

15 W

Frequency

50-60 Hz

50-60 Hz

Measurement Inputs

Nominal supply frequency.fn

50-60 Hz

50-60 Hz

Line-line rms input voltages

380-480 VAC

100 V, 110 V or 120 V

Nominal input current range

>5 A MCMLV line units require three external 5A, 0,5 class secondary current transformers. IEC 60044-1, ANSI 57.13

>5 A All medium/high voltage MCM units require three external 5A secondary current transformers and three 100 V, 110 V or 120 V secondary voltage transformers of appropriate primary inputs

Applicable standards

EN 61000 EN 60950 EN 55011 CE

EN 61000 EN 60950 EN 55011 CE

Nato stock number

6625270131535

6625270131535

Weight

1250 Gr

1250 Gr

These units can be connected to Local Area Network (LAN) using TCP / IP-RS 422/485 converters.