Artesis Plant Condition Monitor (PCM)
Technical Specifications
|
PCM LV |
PCM MV & HV |
|---|---|---|
Dimensions |
96mm x 96mm x 140mm Front panel mounting |
96mm x 96mm x 140mm Front panel mounting |
Enclosure |
Aluminium, RAL 7032 surface protection |
Aluminium, RAL 7032 surface protection |
Operations |
Continuous |
Continuous |
Ambient temperature |
0-40c (Humidity %90 RH non-condensing) |
0-40c (Humidity %90 RH non-condensing) |
Class |
IP20 |
IP20 |
Applicable power range |
Low voltage generators |
Medium and high voltage generators |
Interfaces |
RS 485 serial I/0, Modbus, Artebus |
RS 485 serial I/0, Modbus, Artebus |
Digital outputs |
1 assignable relay output, user programmable NC/NO contacts |
1 assignable relay output, user programmable NC/NO contacts |
Update period |
60-120 seconds |
60-120 seconds |
Input Line Power Specifications | ||
Voltage |
90-240 VAC |
90-240 VAC |
Power |
15 W |
15 W |
Frequency |
50-60 Hz |
50-60 Hz |
Measurement Inputs | ||
Nominal supply frequency.fn |
50-60 Hz |
50-60 Hz |
Line-line rms input voltages |
380-480 VAC |
100 V, 110 V or 120 V |
Nominal input current range |
>5 A MCMLV line units require three external 5A, 0,5 class secondary current transformers. IEC 60044-1, ANSI 57.13 |
>5 A All medium/high voltage MCM units require three external 5A secondary current transformers and three 100 V, 110 V or 120 V secondary voltage transformers of appropriate primary inputs |
Applicable standards |
EN 61000 EN 60950 EN 55011 CE |
EN 61000 EN 60950 EN 55011 CE |
Nato stock number |
6625270131535 |
6625270131535 |
Weight |
1250 Gr |
1250 Gr |
These units can be connected to Local Area Network (LAN) using TCP / IP-RS 422/485 converters.